Type designation |
SG125CX-P2 |
Input (DC) |
|
Recommended max. PV input power |
175 kW |
Max. PV input voltage |
1100 V |
Min. PV input voltage / Startup input voltage |
180 V / 200 V |
Rated PV input voltage |
600 V |
MPP voltage range |
180 – 1000 V |
No. of independent MPP inputs |
12 |
No. of PV strings per MPPT |
2 |
Max. PV input current |
360 A (30 A *12) |
Max. DC short-circuit current |
480 A (40 A * 12) |
Max. current for DC connector |
20 A |
Output (AC) |
|
Max. AC Output power |
125 kVA |
Rated AC output apparent power |
125 kVA |
Max. AC output current |
181.1 A |
Rated AC output current (at 230V) |
181.1 A |
Rated AC voltage |
3 / N / PE, 230 / 400 V |
AC voltage range |
320 – 480V |
Rated grid frequency |
50 Hz / 60 Hz |
Grid frequency range |
45 – 55 Hz / 55 – 65 Hz |
Harmonic (THD) |
< 3 % (at rated power) |
Power factor at rated power / Adjustable power factor |
> 0.99 / 0.8 leading – 0.8 lagging |
Feed-in phases / connection phases |
3 / 3-N-PE |
Efficiency |
|
Max. efficiency / European efficiency |
98.5% / 98.3% |
Protection |
|
Grid monitoring |
Yes |
DC reverse polarity protection |
Yes |
AC short circuit protection |
Yes |
Leakage current protection |
Yes |
Surge protection |
DC Type I + II / AC Type II |
Ground fault monitoring |
Yes |
DC switch |
Yes |
PV string monitoring |
Yes |
Q at night function |
Yes |
Arc fault circuit interrupter (AFCI) |
Yes |
PID recovery function |
Yes |
General Data |
|
Dimensions (W*H*D) |
1020*795*360mm |
Mounting Method |
Wall-mounting bracket |
Weight |
87 kg |
Topology |
Transformerless |
Degree of protection |
IP66 |
Corrosion |
C5 |
Night power consumption |
< 5 W |
Operating ambient temperature range |
-30 to 60°C |
Allowable relative humidity range (non-condensing) |
0 – 100 % |
Cooling method |
Smart forced air cooling |
Max. operating altitude |
4000 m (> 3000 m derating) |
Display |
LED, Bluetooth+APP |
Communication |
RS485 / Optional: WLAN, Ethernet |
DC connection type |
Evo2 (Max. 6 mm²) |
AC connection type |
OT / DT terminal (Max. 240 mm²) |
Grid Compliance |
IEC 62109-1, EN/IEC 61000-6-1/2/3/4, IEC 61727, IEC 62116, EN 50549-1/2, UTE C15-712-1, VDE V 0126-1-1, VDE-AR-N 4105:2018, VFR 2019, NC RfG, G99, UNE 217002, NTS, CEI 0-21 2019, CEI0-16 2019, NRS-097-2-1 |
Grid Support |
Q at night function, LVRT, HVRT, active & reactive power control and power ramp rate control |