Efficiency |
Max. Efficiency |
98.6% @ 400 V, 98.8% @ 480 V |
European Efficiency |
98.4% @ 400 V, 98.6% @ 480 V |
Input |
Max. Input Voltage |
1,100 V |
Max. Current per MPPT |
30 A |
Max. Current per Input |
20 A |
Max. Short Circuit Current per MPPT |
40 A |
Start Voltage |
200 V |
MPPT Operating Voltage Range |
200 V ~ 1,000 V |
Nominal Input Voltage |
600 V @ 400 Vac, 720 V @ 480 Vac |
Number of MPP trackers |
10 |
Max. input number per MPP tracker |
2 |
Output |
Nominal AC Active Power |
115,000 W |
Max. AC Apparent Power |
125,000 VA |
Max. AC Active Power (cosφ=1) |
125,000 W |
Nominal Output Voltage |
400 V / 480 V, 3W+(N)+PE |
Rated AC Grid Frequency |
50 Hz / 60 Hz |
Nominal Output Current |
166.0 A @ 400 V, 138.4 A @ 480 V |
Max. Output Current |
182.3 A @ 400 V, 151.9 A @ 480 V |
Adjustable Power Factor Range |
0.8 leading... 0.8 lagging |
Protection |
Input-side Disconnection Device |
Yes |
Anti-islanding Protection |
Yes |
AC Overcurrent Protection |
Yes |
DC Reverse-polarity Protection |
Yes |
PV-array String Fault Monitoring |
Yes |
DC Surge Arrester Type |
Type II |
AC Surge Arrester Type |
Type II |
DC Insulation Resistance Detection |
Yes |
Residual Current Monitoring Unit |
Yes |
Smart String Level Disconnector |
Yes |
Communication |
Display |
LED indicators; WLAN adaptor + FusionSolar APP |
RS485 |
Yes |
USB |
Yes |
Smart Dongle-4G |
4G / 3G / 2G via Smart Dongle – 4G (Optional) |
Monitoring BUS (MBUS) |
Yes (isolation transformer required) |
General Data |
Dimensions (W x H x D) |
1,035 x 700 x 365 mm |
Weight (with mounting plate) |
93 kg |
Operating Temperature Range |
-25°C ~ 60°C |
Cooling Method |
Smart Air Cooling |
Max. Operating Altitude |
4,000 m (13,123 ft.) |
Relative Humidity |
0 ~ 100% |
DC Connector |
Staubli MC4 |
AC Connector |
Waterproof Connector + OT/DT Terminal |
Protection Degree |
IP66 |
Topology |
Transformerless |
Nighttime Power Consumption |
< 3.5 W |
Standard Compliance |
Certificate: EN 62109-1/-2, IEC 62109-1/-2, EN 50530, IEC 62116, IEC 61727, IEC 60068, IEC 61683 |
Grid Connection Standards: VDE-AR-N4105, EN 50549-1, EN 50549-2, RD 661, RD 1699, C10/11 |